Function Block; Input And Output Signals; Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
5.2.4
5.2.5
5.2.6
Table 86:
HZPDIF (87) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
AlarmPickup
2 - 500
tAlarm
0.000 - 60.000
TripPickup
5 - 900
R series
10 - 20000
Technical reference manual

Function block

HZPDIF (87)
ISI*
TRIP
BLOCK
ALARM
BLKTR
MEASVOLT
ANSI05000363-2-en.vsd
ANSI05000363 V2 EN
Figure 66:
HZPDIF (87) function block

Input and output signals

Table 84:
HZPDIF (87) Input signals
Name
Type
ISI
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
Table 85:
HZPDIF (87) Output signals
Name
Type
TRIP
BOOLEAN
ALARM
BOOLEAN
MEASVOLT
REAL

Setting parameters

Unit
Step
-
-
V
1
s
0.001
V
1
ohm
1
Default
Description
-
Group signal for current input
0
Block of function
0
Block of trip
Description
Trip signal
Alarm signal
Measured RMS voltage on CT secondary side
Default
Description
Disabled
Disable/Enable Operation
10
Alarm voltage level on CT secondary
5.000
Time delay to activate alarm
100
Pickup voltage level in volts on CT secondary
side
250
Value of series resistor in Ohms
Section 5
Differential protection
163