ABB Relion 670 Series Technical Reference Manual page 930

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 15
Monitoring
Name
Values (Range)
I1LimHys
0.000 - 100.000
I1AngZeroDb
0 - 100000
I1AngMin
-180.000 - 180.000
I2ZeroDb
0 - 100000
I2HiHiLim
0.000 -
10000000000.000
I2HiLim
0.000 -
10000000000.000
I2LowLim
0.000 -
10000000000.000
I2LowLowLim
0.000 -
10000000000.000
I2AngZeroDb
0 - 100000
I2AngMax
-180.000 - 180.000
Table 562:
VMSQI Non group settings (basic)
Name
Values (Range)
3V0DbRepInt
1 - 300
3V0Min
0.000 -
10000000000.000
3V0Max
0.000 -
10000000000.000
3V0RepTyp
Cyclic
Dead band
Int deadband
3V0LimHys
0.000 - 100.000
3V0AngDbRepInt
1 - 300
Operation
Disabled
Enabled
3V0AngZeroDb
0 - 100000
3V0AngMin
-180.000 - 180.000
3V0AngMax
-180.000 - 180.000
3V0AngRepTyp
Cyclic
Dead band
Int deadband
V1DbRepInt
1 - 300
Table continues on next page
924
Unit
Step
Default
%
0.001
5.000
m%
1
0
Deg
0.001
-180.000
m%
1
0
A
0.001
900.000
A
0.001
800.000
A
0.001
0.000
A
0.001
0.000
m%
1
0
Deg
0.001
180.000
Unit
Step
Default
Type
1
10
V
0.001
0.000
V
0.001
300000.000
-
-
Cyclic
%
0.001
5.000
Type
1
10
-
-
Disabled
m%
1
0
Deg
0.001
-180.000
Deg
0.001
180.000
-
-
Cyclic
Type
1
10
1MRK505222-UUS C
Description
Hysteresis value in % of range and is
common for all limits
Zero point clamping in 0.001% of range
Minimum value
Zero point clamping in 0.001% of range
High High limit (physical value)
High limit (physical value)
Low limit (physical value)
Low Low limit (physical value)
Zero point clamping in 0.001% of range
Maximum value
Description
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Minimum value
Maximum value
Reporting type
Hysteresis value in % of range and is
common for all limits
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Disbled/Enabled operation
Zero point clamping in 0.001% of range
Minimum value
Maximum value
Reporting type
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Technical reference manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670

Table of Contents