ABB Relion 670 Series Technical Reference Manual page 678

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 12
Control
EXE_CL
OPENPOS
CLOSEPOS
tStartMove timer
tIntermediate timer
IEC05000097 V1 EN
Figure 338:
The timers tStartMove and tIntermediate
672
Close pulse duration
t1
tStartMove
The timers tOpenPulse and tClosePulse are the length of the execute output pulses to
be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be adaptive
with the configuration parameter AdaptivePulse. Figure
execute output pulse. The AdaptivePulse parameter will have affect on both execute
output pulses.
OPENPOS
CLOSEPOS
EXE_CL
EXE_CL
IEC05000098 V1 EN
Figure 339:
Execute output pulse
t2
tIntermediate
tClosePulse
tClosePulse
1MRK505222-UUS C
AdaptivePulse = TRUE
if t1 > tStartMove then
"switch-not-start-moving"
attribute in 'cause' is set
if t2 > tIntermediate then
"persisting-intermediate-state"
attribute in 'cause' is set
en05000097.vsd
339
shows the principle of the
AdaptivePulse=FALSE
AdaptivePulse=TRUE
en05000098.vsd
Technical reference manual