Input And Output Signals - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Impedance protection
6.1.5
190
ZMQAPDIS (21)
I3P*
TRIP
V3P*
TR_A
BLOCK
TR_B
LOVBZ
TR_C
BLKTR
PICKUP
PHSEL
PU_A
DIRCND
PU_B
PU_C
PHPUND
ANSI09000884-1-en.vsd
ANSI09000884 V1 EN
Figure 85:
ZMQAPDIS (21) function block (zone 2 - 5)
ZDRDIR
I3P*
STDIRCND
U3P*
IEC10000007-1-en.vsd
IEC10000007 V1 EN
Figure 86:
ZDRDIR (21D) function block

Input and output signals

Table 93:
ZMQPDIS (21) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
LOVBZ
BOOLEAN
BLKTR
BOOLEAN
PHSEL
INTEGER
DIRCND
INTEGER
Table 94:
ZMQPDIS (21) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
PICKUP
BOOLEAN
Table continues on next page
Default
Description
-
Group signal for current input
-
Group signal for voltage input
0
Block of function
0
Blocks all output for LOV (or fuse failure) condition
0
Blocks all trip outputs
0
Faulted phase loop selection enable from phase
selector
0
External directional condition
Description
General Trip, issued from any phase or loop
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
General Pickup, issued from any phase or loop
1MRK505222-UUS C
Technical reference manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670