ABB Relion 670 Series Technical Reference Manual page 809

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
13.2.5
Table 426:
ZC1PPSCH (85) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Scheme Type
Disabled
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord
0.000 - 60.000
tSendMin
0.000 - 60.000
13.2.6
13.3
Technical reference manual
Setting parameters
Unit
Step
-
-
-
-
s
0.001
s
0.001
Technical data
Table 427:
ZC1PPSCH (85) technical data
Function
Scheme type
Co-ordination time for blocking
communication scheme
Minimum duration of a carrier send
signal
Security timer for loss of carrier
guard detection
Operation mode of unblocking logic
Current reversal and WEI logic for distance protection
3-phase ZCRWPSCH (85)
Function description
Current reversal and weak-end infeed
logic for distance protection
Scheme communication
Default
Description
Disabled
Operation Enable / Disable
Permissive UR
Scheme type
0.000
Trip coordinate time
0.100
Minimum duration of Carrier Send signal
Range or value
Intertrip
Permissive UR
Permissive OR
Blocking
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
Off
NoRestart
Restart
IEC 61850
IEC 60617
identification
identification
ZCRWPSCH
Section 13
Accuracy
-
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
-
ANSI/IEEE C37.2
device number
-
85