Section 7
Current protection
7.9.4
7.9.5
Table 226:
STBPTOC (50STB) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
EnableMode
Release
Continuous
IPickup
1 - 2500
Table 227:
STBPTOC (50STB) Group settings (advanced)
Name
Values (Range)
t
0.000 - 60.000
464
Input and output signals
Table 224:
STBPTOC (50STB) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
ENABLE
BOOLEAN
Table 225:
STBPTOC (50STB) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
Setting parameters
Unit
Step
-
-
A
1
-
-
%IB
1
Unit
Step
s
0.001
Default
Description
-
Three phase currents
0
Block of function
0
Block of trip
0
Enable stub protection usually with open disconnect
switch (89b)
Description
Trip
Pickup
Default
Description
Disabled
Disable/Enable Operation
3000
Base current
Release
Enable stub protection usually with open
disconnect switch (89b)
200
Pickup current level in % of IBase
Default
Description
0.000
Time delay