Name
Values (Range)
OpenCTEnable
Disabled
Enabled
tOCTAlarmDelay
0.100 - 10.000
tOCTResetDelay
0.100 - 10.000
Table 81:
LT6CPDIF (87LT) Non group settings (basic)
Name
Values (Range)
NoOfTerminals
2
3
4
5
6
Chan2IsLocal
No
Yes
IBase
50.0 - 9999.9
ZerSeqCurSubtr
Disabled
Enabled
TraAOnInpCh
No Transf A
1
2
3
4
5
6
RatVoltW1TraA
1.0 - 9999.9
RatVoltW2TraA
1.0 - 9999.9
ClockNumTransA
0 [0 deg]
1 [30 deg lag]
2 [60 deg lag]
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg lag]
7 [210 deg lag]
8 [240 deg lag]
9 [270 deg lag]
10 [300 deg lag]
11 [330 deg lag]
ZerSeqPassTraA
No
Yes
Table continues on next page
Technical reference manual
Unit
Step
Default
-
-
Enabled
s
0.001
1.000
s
0.001
0.250
Unit
Step
Default
-
-
2
-
-
No
A
0.1
3000.0
-
-
Disabled
-
-
No Transf A
kV
0.1
130.0
kV
0.1
130.0
-
-
0 [0 deg]
-
-
No
Differential protection
Description
Open CTEnable Off/On
Open CT: time in s to alarm after an open CT
is detected
Reset delay in s. After delay, diff. function is
activated
Description
Number of current terminals of the protected
circuit
2-nd local current connected to input channel
2, Yes/ No
Base (reference) current of the differential
protection
Off/On for elimination of zero seq. from diff.
and bias curr
Power transformer A applied on input channel
X
Transformer A rated voltage (kV) on winding
1 (HV winding)
Transformer A rated voltage (kV) on winding
2 (LV winding)
Transf. A phase shift in multiples of 30 deg, 5
for 150 deg
Yes/No for capability of transf A to transform
zero seq curr
Section 5
159