Table 260:
OV2PTOV (59) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
VBase
0.05 - 2000.00
OperationStep1
Disabled
Enabled
Characterist1
Definite time
Inverse curve A
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode1
1 out of 3
2 out of 3
3 out of 3
Pickup1
1 - 200
t1
0.00 - 6000.00
t1Min
0.000 - 60.000
TD1
0.05 - 1.10
HystAbs1
0.0 - 100.0
OperationStep2
Disabled
Enabled
Table continues on next page
Technical reference manual
Name
Type
TRST2_B
BOOLEAN
TRST2_C
BOOLEAN
PICKUP
BOOLEAN
PU_ST1
BOOLEAN
PU_ST1_A
BOOLEAN
PU_ST1_B
BOOLEAN
PU_ST1_C
BOOLEAN
PU_ST2
BOOLEAN
PU_ST2_A
BOOLEAN
PU_ST2_B
BOOLEAN
PU_ST2_C
BOOLEAN
Setting parameters
Unit
Step
-
-
kV
0.05
-
-
-
-
-
-
%VB
1
s
0.01
s
0.001
-
0.01
%VB
0.1
-
-
Description
Trip signal from step2 phase B
Trip signal from step2 phase C
General pickup signal
Common pickup signal from step1
Pickup signal from step1 phase A
Pickup signal from step1 phase B
Pickup signal from step1 phase C
Common pickup signal from step2
Pickup signal from step2 phase A
Pickup signal from step2 phase B
Pickup signal from step2 phase C
Default
Description
Disabled
Disable/Enable Operation
400.00
Base voltage
Enabled
Enable execution of step 1
Definite time
Selection of time delay curve type for step 1
1 out of 3
Number of phases required for op (1 of 3, 2 of
3, 3 of 3) from step 1
120
Voltage pickup value (Definite-Time & Inverse-
Time curve) in % of VBase, step 1
5.00
Definitive time delay of step 1
5.000
Minimum operate time for inverse curves for
step 1
0.05
Time multiplier for the inverse time delay for
step 1
0.5
Absolute hysteresis in % of VBase, step 1
Enabled
Enable execution of step 2
Section 8
Voltage protection