ABB Relion 670 Series Technical Reference Manual page 551

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
8.5.5
Table 277:
VDCPTOV (60) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
VBase
0.50 - 2000.00
BlkDiffAtVLow
No
Yes
VDTrip
0.0 - 100.0
tTrip
0.000 - 60.000
tReset
0.000 - 60.000
V1Low
0.0 - 100.0
V2Low
0.0 - 100.0
tBlock
0.000 - 60.000
VDAlarm
0.0 - 100.0
tAlarm
0.000 - 60.000
Table 278:
VDCPTOV (60) Group settings (advanced)
Name
Values (Range)
RF_A
0.000 - 3.000
RF_B
0.000 - 3.000
RF_C
0.000 - 3.000
8.5.6
Technical reference manual
Setting parameters
Unit
Step
-
-
kV
0.01
-
-
%VB
0.1
s
0.001
s
0.001
%VB
0.1
%VB
0.1
s
0.001
%VB
0.1
s
0.001
Unit
Step
-
0.001
-
0.001
-
0.001
Technical data
Table 279:
VDCPTOV (60) technical data
Function
Voltage difference for alarm and
trip
Under voltage level
Timers
Default
Description
Disabled
Operation Enable/Disable
400.00
Base Voltage
Yes
Block operation at low voltage
5.0
Operate level, in % of VBase
1.000
Time delay for voltage differential operate, in
milliseconds
0.000
Time delay for voltage differential reset, in
seconds
70.0
Input 1 undervoltage level, in % of VBase
70.0
Input 2 undervoltage level, in % of VBase
0.000
Reset time for undervoltage block
2.0
Alarm level, in % of VBase
2.000
Time delay for voltage differential alarm, in
seconds
Default
Description
1.000
Ratio compensation factor phase L1
U2L1*RFL1=U1L1
1.000
Ratio compensation factor phase L2
U2L2*RFL2=U1L2
1.000
Ratio compensation factor phase L3
U2L3*RFL3=U1L3
Range or value
VBase
(0.0–100.0) % of
VBase
(0.0–100.0) % of
(0.000–60.000)s
Section 8
Voltage protection
Accuracy
± 0.5 % of V
n
± 0.5% of V
n
± 0.5% ± 10 ms
545