ABB Relion 670 Series Technical Reference Manual page 872

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 14
Logic
14.1.4
866
Input and output signals
Table 491:
SMPPTRC (94) Input signals
Name
Type
BLOCK
BOOLEAN
BLKLKOUT
BOOLEAN
TRINP_3P
BOOLEAN
TRINP_A
BOOLEAN
TRINP_B
BOOLEAN
TRINP_C
BOOLEAN
PS_A
BOOLEAN
PS_B
BOOLEAN
PS_C
BOOLEAN
1PTRZ
BOOLEAN
1PTRGF
BOOLEAN
P3PTR
BOOLEAN
SETLKOUT
BOOLEAN
RSTLKOUT
BOOLEAN
Table 492:
SMPPTRC (94) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
TR1P
BOOLEAN
TR2P
BOOLEAN
TR3P
BOOLEAN
CLLKOUT
BOOLEAN
Default
Description
0
Block of function
0
Blocks circuit breaker lockout output (CLLKOUT)
0
Trip all phases
0
Trip phase A
0
Trip phase B
0
Trip phase C
0
Input from phase selection, phase A
0
Input from phase selection, phase B
0
Input from phase selection, phase C
0
Zone Trip with a separate phase selection
0
Single phase Directional Ground Fault Overcurrent
Trip with phase selection
0
Prepare all tripping to be three-phase
0
Input for setting the circuit breaker lockout function
0
Input for resetting the circuit breaker lockout function
Description
General trip output signal
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
Tripping single-pole
Tripping two-pole
Tripping three-pole
Circuit breaker lockout output (set until reset)
1MRK505222-UUS C
Technical reference manual