Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
6.13.5
Table 171:
PSPPPAM (78) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OperationZ1
Disabled
Enabled
OperationZ2
Disabled
Enabled
ImpedanceZA
0.00 - 1000.00
ImpedanceZB
0.00 - 1000.00
ImpedanceZC
0.00 - 1000.00
AnglePhi
72.00 - 90.00
StartAngle
0.0 - 180.0
TripAngle
0.0 - 180.0
N1Limit
1 - 20
N2Limit
1 - 20
Table 172:
PSPPPAM (78) Group settings (advanced)
Name
Values (Range)
ResetTime
0.000 - 60.000
Technical reference manual
Name
Type
SLIPZOHM
REAL
SLIPZPER
REAL
VCOS
REAL
VCOSPER
REAL

Setting parameters

Unit
Step
-
-
-
-
-
-
%
0.01
%
0.01
%
0.01
Deg
0.01
Deg
0.1
Deg
0.1
-
1
-
1
Unit
Step
s
0.001
Description
Slip impedance in ohms
Slip impedance in percent of ZBase
UCosPhi voltage
VCosPhi voltage in percent of VBase
Default
Description
Disabled
Operation Enable / Disable
Enabled
Operation Enable/Disable zone Z1
Enabled
Operation Enable/Disable zone Z2
10.00
Forward impedance in % of Zbase
10.00
Reverse impedance in % of Zbase
10.00
Impedance of zone1 limit in % of Zbase
85.00
Angle of the slip impedance line
110.0
Rotor angle for the pickup signal
90.0
Rotor angle for the trip1 and trip2 signals
1
Count limit for the trip1 signal
3
Count limit for the trip2 signal
Default
Description
5.000
Time without slip to reset all signals
Section 6
Impedance protection
367