ABB Relion 670 Series Technical Reference Manual page 546

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 8
Voltage protection
8.4.4
8.4.5
Table 271:
OEXPVPH (24) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
Pickup1
100.0 - 180.0
Pickup2
100.0 - 200.0
XLeakage
0.000 - 200.000
t_TripPulse
0.000 - 60.000
t_MinTripDelay
0.000 - 60.000
t_MaxTripDelay
0.00 - 9000.00
t_CoolingK
0.10 - 9000.00
CurveType
IEEE
Tailor made
Table continues on next page
540
Input and output signals
Table 269:
OEXPVPH (24) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
RESET
BOOLEAN
Table 270:
OEXPVPH (24) Output signals
Name
Type
TRIP
BOOLEAN
PICKUP
BOOLEAN
ALARM
BOOLEAN
Setting parameters
Unit
Step
-
-
A
1
kV
0.05
%VB/f
0.1
%VB/f
0.1
ohm
0.001
s
0.001
s
0.001
s
0.01
s
0.01
-
-
Default
Description
-
Current connection
-
Voltage connection
0
Block of function
0
Reset operation
Description
Trip from overexcitation function
Overexcitation above set trip pickup (instantaneous)
Overexcitation above set alarm pickup (delayed)
Default
Description
Disabled
Disable/Enable Operation
3000
Base current (rated phase current) in A
400.00
Base voltage (main voltage) in kV
110.0
Operate level of V/Hz at no load and rated
freq in % of (Vbase/frated)
140.0
High level of V/Hz above which tMin is used,
in % of (Vbase/fn)
0.000
Winding leakage reactance in primary ohms
0.100
Length of the pulse for trip signal (in sec)
7.000
Minimum trip delay for V/Hz inverse curve, in
sec
1800.00
Maximum trip delay for V/Hz inverse curve, in
sec
1200.00
Transformer magnetic core cooling time
constant, in sec
IEEE
Inverse time curve selection, IEEE/Tailor made
1MRK505222-UUS C
Technical reference manual