Table 421:
ZCPSCH (85) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
SchemeType
Disabled
Intertrip
Permissive UR
Permissive OR
Blocking
tCoord
0.000 - 60.000
tSendMin
0.000 - 60.000
Table 422:
ZCPSCH (85) Group settings (advanced)
Name
Values (Range)
Unblock
Disabled
NoRestart
Restart
tSecurity
0.000 - 60.000
13.1.6
Technical reference manual
Setting parameters
Unit
Step
-
-
-
-
s
0.001
s
0.001
Unit
Step
-
-
s
0.001
Technical data
Table 423:
ZCPSCH (85) technical data
Function
Scheme type
Co-ordination time for blocking
communication scheme
Minimum duration of a send signal
Security timer for loss of guard
signal detection
Operation mode of unblocking logic
Scheme communication
Default
Description
Disabled
Disable/Enable Operation
Permissive UR
Scheme type
0.035
Communication scheme channel coordination
time
0.100
Minimum duration of a carrier send signal
(carrier continuation)
Default
Description
Disabled
Operation mode of unblocking logic
0.035
Security timer for loss of carrier guard detection
Range or value
Intertrip
Permissive Underreach
Permissive Overreach
Blocking
(0.000-60.000) s
(0.000-60.000) s
(0.000-60.000) s
Disabled
NoRestart
Restart
Section 13
Accuracy
-
± 0.5% ± 10 ms
± 0.5% ± 10 ms
± 0.5% ± 10 ms
-
795