Section 13
Scheme communication
13.8.3.5
Table 454:
COUVGAPC (59_27) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
VBase
0.05 - 2000.00
OperationUV
Disabled
Enabled
27_COMP
1 - 100
tUV
0.000 - 60.000
OperationOV
Disabled
Enabled
59_COMP
1 - 200
tOV
0.000 - 60.000
Table 455:
COUVGAPC (59_27) Group settings (advanced)
Name
Values (Range)
HystAbs
0.0 - 100.0
838
Name
Type
59 PU
BOOLEAN
27_PU_A
BOOLEAN
27_PU_B
BOOLEAN
27_PU_C
BOOLEAN
59_PU_A
BOOLEAN
59_PU_B
BOOLEAN
59_PU_C
BOOLEAN
Setting parameters
Unit
Step
-
-
kV
0.05
-
-
%VB
1
s
0.001
-
-
%VB
1
s
0.001
Unit
Step
%VB
0.1
Description
Pick up for overvoltage
pick up for 27 phase A uncompensated
pick up for 27 phase B uncompensated
pickup for compensated 27 phase C
pick up for uncompensated 59 phase A
pick up for uncompensated 59 phase B
pick up for uncompensated 59 phase C
Default
Description
Disabled
Operation Enable/Disable
400.00
Base setting for voltage in kV
Enabled
Operation compensated under voltage Off/On
70
Compensated under voltage level in % of
VBase
1.000
Time delay to trip under voltage
Enabled
Operation compensated over voltage Off/On
120
Compensated over voltage level in % of VBase
5.000
Time delay to trip over voltage
Default
Description
0.5
Hysteresis absolute for compensated over/
under voltage in % of VBase
1MRK505222-UUS C