ABB Relion 670 Series Technical Reference Manual page 618

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 11
Secondary system supervision
11.2.5
Table 313:
SDDRFUF Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
VBase
0.05 - 2000.00
OpModeSel
Disabled
V2I2
V0I0
V0I0 OR V2I2
V0I0 AND V2I2
OptimZsNs
3V0PU
1 - 100
3I0PU
1 - 100
3V2PU
1 - 100
3I2PU
1 - 100
OpDVDI
Disabled
Enabled
DVPU
1 - 100
DIPU
1 - 100
VPPU
1 - 100
IPPU
1 - 100
SealIn
Disabled
Enabled
VSealInPU
1 - 100
IDLDPU
1 - 100
VDLDPU
1 - 100
612
Setting parameters
Unit
Step
-
-
A
1
kV
0.05
-
-
%VB
1
%IB
1
%VB
1
%IB
1
-
-
%VB
1
%IB
1
%VB
1
%IB
1
-
-
%VB
1
%IB
1
%VB
1
Default
Description
Enabled
Disable/Enable Operation
3000
Base current
400.00
Base voltage
V0I0
Operating mode selection
30
Pickup of residual overvoltage element in %
of VBase
10
Pickup of residual undercurrent element in %
of IBase
30
Pickup of negative sequence overvoltage
element in % of VBase
10
Pickup of negative sequence undercurrent
element in % of IBase
Disabled
Operation of change based function Disable/
Enable
60
Pickup of change in phase voltage in % of
VBase
15
Pickup of change in phase current in % of
IBase
70
Pickup of phase voltage in % of VBase
10
Pickup of phase current in % of IBase
Enabled
Seal in functionality Disable/Enable
70
Pickup of seal-in phase voltage in % of VBase
5
Pickup for phase current detection in % of
IBase for dead line detection
60
Pickup for phase voltage detection in % of
VBase for dead line detection
1MRK505222-UUS C