ABB Relion 670 Series Technical Reference Manual page 299

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Technical reference manual
|3V
|>V
| · 0.2
0
1
|V
|> VBase · 0.2/√(3)
1
and
3I
<0.1 · IBase
0
or
3I
<maxIph · INRelPG
0
where:
3V
is the magnitude of the zero sequence voltage
0
V
is the magnitude of the negative sequence voltage at the relay measuring point of
2
phase A
k5
is design parameter
ILmax
is the maximal phase current
IMinOp
is the setting of minimum operate phase current in % of
Phase-to-phase fault detection
The detection of phase-to-phase fault is performed by evaluation of the angle
difference between the sequence voltages V
C-A sector
VB
180°
A-B sector
ANSI06000383 V2 EN
Figure 149:
Definition of fault sectors for phase-to-phase fault
and V
.
2
1
60°
VC
VA (Ref)
B-C sector
VA
300°
ANSI06000383-2-en.vsd
Section 6
Impedance protection
IBase
293