Input And Output Signals; Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Impedance protection
6.8.4
6.8.5
Table 143:
FMPSPDIS Group settings (basic)
Name
Values (Range)
IBase
1 - 99999
VBase
0.05 - 2000.00
IMaxLoad
10 - 5000
RLd
1.00 - 3000.00
LdAngle
5 - 70
302

Input and output signals

Table 141:
FMPSPDIS Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
ZSTART
BOOLEAN
TR3PH
BOOLEAN
1POLEAR
BOOLEAN
Table 142:
FMPSPDIS Output signals
Name
Type
PU_A
BOOLEAN
PU_B
BOOLEAN
PU_C
BOOLEAN
PHG_FLT
BOOLEAN
PHSCND
INTEGER
PLECND
INTEGER
DLECND
INTEGER
PICKUP
BOOLEAN

Setting parameters

Unit
Step
A
1
kV
0.05
%IB
1
ohm/p
0.01
Deg
1
Default
Description
-
Group signal for current
-
Group signal for voltage
0
Block of function
0
Start from underimpdeance function
0
Three phase tripping initiated
0
Single pole autoreclosing in progress
Description
Fault detected in phase A
Fault detected in phase B
Fault detected in phase C
Ground fault detected
Binary coded starts from phase selection
Binary coded starts from ph sel with load encroachment
Binary coded starts from load encroachment only
Indicates that something has picked up
Default
Description
3000
Base current
400.00
Base voltage
200
Maximum load for identification of three
phase fault in % of IBase
80.00
Load encroachment resistive reach in ohm/
phase
20
Load encroachment inclination of load
angular sector
1MRK505222-UUS C