ABB Relion 670 Series Technical Reference Manual page 457

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Technical reference manual
(
Q = Q
+ Q
- Q
-
n
n
1
final
EQUATION1168 V1 EN
where:
is the calculated present temperature,
Q
n
is the calculated temperature at the previous time step,
Q
n-1
is the calculated final temperature with the actual current,
Q
final
is the time step between calculation of the actual temperature and
Dt
t
is the set thermal time constant for the protected device (line or cable)
The actual temperature of the protected component (line or cable) is calculated by
adding the ambient temperature to the calculated temperature, as shown above. The
ambient temperature can be taken from a separate sensor or can be given a constant
value. The calculated component temperature is available as a real figure signal, TEMP.
When the component temperature reaches the set alarm level AlarmTemp the output
signal ALARM is set. When the component temperature reaches the set trip level
TripTemp the output signal TRIP is set.
There is also a calculation of the present time to operate with the present current. This
calculation is only performed if the final temperature is calculated to be above the
operation temperature:
æ
Q
t
= - × ç
final
t
ln
ç
operate
Q
è
final
EQUATION1169 V1 EN
The calculated time to trip is available as a real figure signal, TTRIP.
After a trip, caused by the thermal overload protection, there can be a lockout to
reconnect the tripped circuit. The output lockout signal LOCKOUT is activated when
the device temperature is above the set lockout release temperature setting ReclTemp.
The time to lockout release is calculated that is, a calculation of the cooling time to a
set value. The thermal content of the function can be reset with input RESET.
æ
D
ö
t
)
-
×
-
1
e
t
ç
÷
-
n
1
è
ø
ö
- Q
operate
÷
÷
- Q
ø
n
Section 7
Current protection
(Equation 93)
(Equation 94)
451