ABB Relion 670 Series Technical Reference Manual page 635

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
12.1.5
Table 317:
SESRSYN (25) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
CBConfig
No voltage sel.
Double bus
1 1/2 bus CB
1 1/2 bus alt. CB
Tie CB
VBaseBus
0.001 - 9999.999
VBaseLine
0.001 - 9999.999
PhaseShift
-180 - 180
VRatio
0.040 - 25.000
OperationSynch
Disabled
Enabled
VHighBusSynch
50.0 - 120.0
VHighLineSynch
50.0 - 120.0
VDiffSynch
0.02 - 0.50
FreqDiffMin
0.003 - 0.250
FreqDiffMax
0.050 - 0.250
FreqRateChange
0.000 - 0.500
tBreaker
0.000 - 60.000
tClosePulse
0.050 - 60.000
tMaxSynch
0.00 - 6000.00
tMinSynch
0.000 - 60.000
OperationSC
Disabled
Enabled
VHighBusSC
50.0 - 120.0
VHighLineSC
50.0 - 120.0
VDiffSC
0.02 - 0.50
FreqDiffA
0.003 - 1.000
FreqDiffM
0.003 - 1.000
Table continues on next page
Technical reference manual
Setting parameters
Unit
Step
-
-
-
-
kV
0.001
kV
0.001
Deg
5
-
0.001
-
-
%VBB
1.0
%VBL
1.0
pu
0.01
Hz
0.001
Hz
0.001
Hz/s
0.001
s
0.001
s
0.001
s
0.01
s
0.001
-
-
%VBB
1.0
%VBL
1.0
pu
0.01
Hz
0.001
Hz
0.001
Default
Description
Disabled
Disable/Enable Operation
No voltage sel.
Select CB configuration
400.000
Base value for busbar voltage settings
400.000
Base value for line voltage settings
0
Phase shift
1.000
Voltage ratio
Disabled
Operation for synchronizing function Off/On
80.0
Voltage high limit bus for synchronizing in %
of UBaseBus
80.0
Voltage high limit line for synchrocheck in %
of VBaseLine
0.10
Voltage difference limit for synchronizing in p.u
0.010
Minimum frequency difference limit for
synchronizing
0.200
Maximum frequency difference limit for
synchronizing
0.300
Maximum allowed frequency rate of change
0.080
Closing time of the breaker
0.200
Breaker closing pulse duration
600.00
Resets synch if no close has been made
before set time
2.000
Minimum time to accept synchronizing
conditions
Enabled
Operation for synchronism-check function Off/
On
80.0
Voltage high limit bus for synchrocheck in %
of VBaseBus
80.0
Voltage high limit line for synchrocheck in %
of UBaseLine
0.15
Voltage difference limit in p.u
0.010
Frequency difference limit between bus and
line Auto
0.010
Frequency difference limit between bus and
line Manual
Section 12
Control
629