ABB Relion 670 Series Technical Reference Manual page 1000

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 17
Station communication
17.2.2
Table 611:
IEC61850-8-1 Non group settings (basic)
Name
Values (Range)
Operation
Off
On
GOOSE
Front
OEM311_AB
OEM311_CD
17.2.3
17.2.4
17.2.4.1
17.2.4.2
994
Setting parameters
Unit
Step
-
-
-
-
Technical data
Table 612:
IEC 61850-8-1 communication protocol
Function
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
Protocol
Communication speed for the IEDs
IEC 61850 generic communication I/O functions SPGGIO,
SP16GGIO
Introduction
IEC61850 generic communication I/O functions (SPGGIO) is used to send one single
logical signal to other systems or equipment in the substation.
Principle of operation
Upon receiving a signal at its input, IEC61850 generic communication I/O functions
(SPGGIO) function sends the signal over IEC 61850-8-1 to the equipment or system
that requests this signal. To get the signal, PCM600 must be used to define which
function block in which equipment or system should receive this information.
Default
Description
Off
Operation Off/On
OEM311_AB
Port for GOOSE communication
Value
IEC 61850-8-1
100BASE-FX
IEC 608–5–103
9600 or 19200 Bd
DNP3.0
300–19200 Bd
TCP/IP, Ethernet
100 Mbit/s
1MRK505222-UUS C