Section 14
Logic
14.3.12
Table 528:
TIMERSET Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
t
0.000 - 90000.000
14.3.13
880
Settable timer function block TIMERSET
The Settable timer function block (TIMERSET) timer has outputs for delayed input
signal at drop-out and at pick-up. The timer has a settable time delay. It also has an
Operation setting /Enabled, /Disabled that controls the operation of the timer.
TIMERSET
INPUT
ON
OFF
IEC04000411-2-en.vsd
IEC04000411 V2 EN
Figure 446:
TIMERSET function block
Table 526:
TIMERSET Input signals
Name
Type
INPUT
BOOLEAN
Table 527:
TIMERSET Output signals
Name
Type
ON
BOOLEAN
OFF
BOOLEAN
Unit
Step
-
-
s
0.001
Technical data
Table 529:
Configurable logic blocks
Logic block
Quantity with cycle time
fast
LogicAND
60
LogicOR
60
LogicXOR
10
LogicInverter
30
LogicSRMemory
10
LogicRSMemory
10
Table continues on next page
Default
Description
0
Input to timer
Description
Output from timer, pickup delay
Output from timer, dropout delay
Default
Description
Disabled
Operation Disabled/Enabled
0.000
Delay for settable timer n
Range or value
medium
normal
60
160
-
60
160
-
10
20
-
30
80
-
10
20
-
10
20
-
1MRK505222-UUS C
Accuracy
-
-
-
-
-
-
Technical reference manual