ABB Relion 670 Series Technical Reference Manual page 596

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 10
Multipurpose protection
Name
Values (Range)
TD_OV2
0.05 - 999.00
Operation_UV1
Disabled
Enabled
PickupVolt_UV1
2.0 - 150.0
CurveType_UV1
Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve
tDef_UV1
0.00 - 6000.00
tMin_UV1
0.00 - 6000.00
TD_UV1
0.05 - 999.00
EnBlkLowV_UV1
Disabled
Enabled
BlkLowVolt_UV1
0.0 - 5.0
Operation_UV2
Disabled
Enabled
PickupVolt_UV2
2.0 - 150.0
CurveType_UV2
Definite time
Inverse curve A
Inverse curve B
Prog. inv. curve
tDef_UV2
0.00 - 6000.00
tMin_UV2
0.00 - 6000.00
TD_UV2
0.05 - 999.00
EnBlkLowV_UV2
Disabled
Enabled
BlkLowVolt_UV2
0.0 - 5.0
590
Unit
Step
Default
-
0.01
0.30
-
-
Disabled
%VB
0.1
50.0
-
-
Definite time
s
0.01
1.00
s
0.01
0.05
-
0.01
0.30
-
-
Enabled
%VB
0.1
0.5
-
-
Disabled
%VB
0.1
50.0
-
-
Definite time
s
0.01
1.00
s
0.01
0.05
-
0.01
0.30
-
-
Enabled
%VB
0.1
0.5
1MRK505222-UUS C
Description
Time multiplier for the dependent time delay
for OV2
Disable/Enable operation of UV1
Operate undervoltage level for UV1 in % of
Vbase
Selection of time delay curve type for UV1
Operate time delay in sec for definite time use
of UV1
Minimum operate time for Inverse-Time
curves for UV1
Time multiplier for the dependent time delay
for UV1
Enable internal low voltage level blocking for
UV1
Internal low voltage blocking level for UV1 in
% of Vbase
Disable/Enable operation of UV2
Pickup undervoltage for UV2 in % of Vbase
Selection of time delay curve type for UV2
Operate time delay in sec for definite time use
of UV2
Minimum operate time for Inverse-Time
curves for UV2
Time multiplier for the dependent time delay
for UV2
Enable internal low voltage level blocking for
UV2
Internal low voltage blocking level for UV2 in
% of Vbase
Technical reference manual