1MRK505222-UUS C
Table 610:
ETPMMTR Non group settings (advanced)
Name
Values (Range)
EALim
0.001 -
10000000000.000
ERLim
0.001 -
10000000000.000
DirEnergyAct
Forward
Reverse
DirEnergyReac
Forward
Reverse
EnZeroClamp
Disabled
Enabled
LevZeroClampP
0.001 - 10000.000
LevZeroClampQ
0.001 - 10000.000
EAFPrestVal
0.000 - 10000.000
EARPrestVal
0.000 - 10000.000
ERFPresetVal
0.000 - 10000.000
ERVPresetVal
0.000 - 10000.000
Technical reference manual
Unit
Step
Default
MWh
0.001
1000000.000
MVArh
0.001
1000.000
-
-
Forward
-
-
Forward
-
-
Enabled
MW
0.001
10.000
MVAr
0.001
10.000
MWh
0.001
0.000
MWh
0.001
0.000
MVArh
0.001
0.000
MVArh
0.001
0.000
Section 16
Description
Active energy limit
Reactive energy limit
Direction of active energy flow Forward/
Reverse
Direction of reactive energy flow Forward/
Reverse
Enable of zero point clamping detection
function
Zero point clamping level at active Power
Zero point clamping level at reactive Power
Preset Initial value for forward active energy
Preset Initial value for reverse active energy
Preset Initial value for forward reactive energy
Preset Initial value for reverse reactive energy