Input And Output Signals; Setting Parameters - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 6
Impedance protection
6.11.4
6.11.5
Table 163:
ZMRPSB (68) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
X1InFw
0.10 - 3000.00
R1LIn
0.10 - 1000.00
R1FInFw
0.10 - 1000.00
X1InRv
0.10 - 3000.00
Table continues on next page
354

Input and output signals

Table 161:
ZMRPSB (68) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK_SS
BOOLEAN
BLK_I0
BOOLEAN
BLK1PH
BOOLEAN
REL1PH
BOOLEAN
BLK2PH
BOOLEAN
REL2PH
BOOLEAN
I0CHECK
BOOLEAN
TRSP
BOOLEAN
EXT_PSD
BOOLEAN
Table 162:
ZMRPSB (68) Output signals
Name
Type
PICKUP
BOOLEAN
ZOUT
BOOLEAN
ZIN
BOOLEAN

Setting parameters

Unit
Step
-
-
ohm
0.01
ohm
0.01
ohm
0.01
ohm
0.01
Default
Description
-
Group signal for current input
-
Group signal for voltage input
0
Block of function
0
Block inhibit of start output for slow swing condition
0
Block inhibit of start output for subsequent residual
current detection
0
Block one-out-of-three-phase operating mode
0
Release one-out-of-three-phase operating mode
0
Block two-out-of-three-phase operating mode
0
Release two-out-of-three-phase operating mode
0
Residual current (3I0) detection used to inhibit power
swing detection output
0
Single-pole tripping command issued by tripping
function
0
Input for external detection of power swing
Description
Power swing detected
Measured impedance within outer impedance boundary
Measured impedance within inner impedance boundary
Default
Description
Disabled
Disbled/Enabled operation
30.00
Inner reactive boundary, forward
30.00
Line resistance for inner characteristic angle
30.00
Fault resistance coverage to inner resistive
line, forward
30.00
Inner reactive boundary, reverse
1MRK505222-UUS C
Technical reference manual