ABB Relion 670 Series Technical Reference Manual page 155

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Technical reference manual
Table 67:
LT6CPDIF (87LT) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
TRIPRES
BOOLEAN
TRIPUNRE
BOOLEAN
TRIPENHA
BOOLEAN
PICKUP
BOOLEAN
PU_A
BOOLEAN
PU_B
BOOLEAN
PU_C
BOOLEAN
BLK2H
BOOLEAN
BLK2H_A
BOOLEAN
BLK2H_B
BOOLEAN
BLK2H_C
BOOLEAN
BLK5H
BOOLEAN
BLK5H_A
BOOLEAN
BLK5H_B
BOOLEAN
BLK5H_C
BOOLEAN
OPENCT
BOOLEAN
ALARM
BOOLEAN
OPENCTAL
BOOLEAN
ID_A
REAL
ID_B
REAL
ID_C
REAL
IDMAG_A
REAL
IDMAG_B
REAL
IDMAG_C
REAL
IBIAS
REAL
IDMAG_NS
REAL
Table 68:
LDLPDIF (87L) Input signals
Name
Type
CTFAIL
BOOLEAN
OUTSERV
BOOLEAN
BLOCK
BOOLEAN
Description
Main Trip Signal
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
Trip by restrained differential 87L
Trip by unrestrained differential 87H
Trip by Enhanced restrainted differential 87LEnhanced
Main Pickup output signal
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
Block signal due to second harmonic
Block signal due to second harmonic phase A
Block signal due to second harmonic phase B
Block signal due to second harmonic Phase C
Block signal due to fifth harmonic
Block signal due to fifth harmonic phase A
Block signal due to fifth harmonic phase B
Block signal due to fifth harmonic phase C
An open CT was detected
Alarm for sustained differential current
Open CT Alarm output signal. Issued after a delay ...
Instantaneous differential current, phase A
Instantaneous differential current, phase B
Instantaneous differential current, phase C
Magnitude of fund. freq. differential current, phase A
Magnitude of fund. freq. differential current, phase B
Magnitude of fund. freq. differential current, phase C
Magnitude of the bias current, common for phase A,B.C
Magnitude of the negative sequence differential current
Default
Description
0
CT failure indication from local CT supervision
0
Input for indicating that the IED is out of service
0
Block of function
Section 5
Differential protection
149