Section 12
Control
12.1.3
626
labelled FF must be connected if the available contact indicates that the voltage circuit
is faulty.
The VB1OK/VB2OK and VB1FF/VB2FF inputs are related to the busbar voltage and
the VLNOK and VLNFF inputs are related to the line voltage. Configure them to the
binary input or function outputs that indicate the status of the external fuse failure of
the busbar and line voltages. In the event of a fuse failure, the energizing check
function is blocked. The synchronism check function requires full voltage on both
sides and will be blocked automatically in the event of fuse failures.
Function block
SESRSYN (25)
V3PB1*
SYNOK
V3PB2*
AUTOSYOK
V3PL1*
AUTOENOK
V3PL2*
MANSYOK
BLOCK
MANENOK
BLKSYNCH
TSTSYNOK
BLKSC
TSTAUTSY
BLKENERG
TSTMANSY
BUS1_OP
TSTENOK
BUS1_CL
VSELFAIL
BUS2_OP
B1SEL
BUS2_CL
B2SEL
LINE1_OP
L1SEL
LINE1_CL
L2SEL
LINE2_OP
SYNPROGR
LINE2_CL
SYNFAIL
VB1OK
VOKSYN
VB1FF
VDIFFSYN
VB2OK
FRDIFSYN
VB2FF
FRDIFFOK
VL1OK
FRDERIVA
VL1FF
VOKSC
VL2OK
VDIFFSC
VL2FF
FRDIFFA
STARTSYN
PHDIFFA
TSTSYNCH
FRDIFFM
TSTSC
PHDIFFM
TSTENERG
INADVCLS
AENMODE
VDIFFME
MENMODE
FRDIFFME
PHDIFFME
Vbus
VLine
MODEAEN
MODEMEN
ANSI10000046-1-en.vsd
ANSI10000046 V1 EN
Figure 314:
SESRSYN (25) function block
1MRK505222-UUS C
Technical reference manual