ABB Relion 670 Series Technical Reference Manual page 253

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Technical reference manual
æ
V
-I
ZPP
×
AB
b =
arg
ç
V
-(-I
ZRevPP)
è
×
AB
EQUATION1792-ANSI V1 EN
where
V
is the V
voltage
AB
EQUATION1801 V1 EN
ZRevPP
is the positive sequence impedance setting for phase-to-phase fault in reverse direction
I
jX
AB
I
ZPP
AB
-
Z
Re
vPP
I
AB
ANSI07000110 V1 EN
Figure 119:
Simplified offset mho characteristic and voltage vectors for phase A-to-
B fault.
Operation occurs if 90≤β≤270.
Offset mho, forward direction
When forward direction has been selected for the offset mho, an extra criteria beside
the one for offset mho (90<β<270) is introduced, that is the angle φ between the
voltage and the current must lie between the blinders in second quadrant and fourth
quadrant. See figure 120. Operation occurs if 90≤β≤270 and ArgDir≤φ≤ArgNegRes.
ö
÷
ø
V
=
V
comp1
AB
ß
V
Vcomp2 =
Section 6
Impedance protection
(Equation 35)
-
I
ZPP
AB
·
=IF
V
·ZF =V
AB
I
R
AB
en07000110_ansi.vsd
247