Technical reference manual
to the fault from the currents and voltages at one line end. If this is not done, the
accuracy of the calculated figure will vary with the load flow and the amount of
additional fault resistance.
The calculation algorithm used in the fault locator in compensates for the effect of double-
end infeed, additional fault resistance and load current.
Accurate algorithm for measurement of distance to fault
Figure
469
shows a single-line diagram of a single transmission line, that is fed from
both ends with source impedances Z
distance F from IED A on a line with the length L and impedance Z
resistance is defined as R
algorithm.
F
A
Z
pZ
I
A
L
A
V
A
ANSI01000171 V1 EN
Figure 469:
Fault on transmission line fed from both ends
From figure
469
it is evident that:
=
× ×
+ ×
V
I p Z
I R
A
A
L
F
F
EQUATION1595 V1 EN
Where:
I
is the line current after the fault, that is, pre-fault current plus current change due to the fault,
A
I
is the fault current and
F
is a relative distance to the fault
p
and Z
. Assume that the fault occurs at a
A
B
. A single-line model is used for better clarification of the
F
L
B
(1-p).Z
I
L
B
I
F
R
F
xx01000171_ansi.vsd
Section 15
Monitoring
. The fault
L
Z
B
(Equation 181)
941