1MRK505222-UUS C
Technical reference manual
Analog signals
Binary signals
ANSI09000336 V1 EN
Figure 472:
Disturbance report functions and related function blocks
The whole disturbance report can contain information for a number of recordings, each
with the data coming from all the parts mentioned above. The sequential of events
function is working continuously, independent of disturbance triggering, recording
time, and so on. All information in the disturbance report is stored in non-volatile flash
memories. This implies that no information is lost in case of loss of auxiliary power.
Each report will get an identification number in the interval from 0-999.
Disturbance report
Record no. N
Record no. N+1
General dist.
Indications
information
ANSI05000125 V1 EN
Figure 473:
Disturbance report structure
Up to 100 disturbance reports can be stored. If a new disturbance is to be recorded
when the memory is full, the oldest disturbance report is overwritten by the new one.
The total recording capacity for the disturbance recorder is depending of sampling
A1-4RADR
A4RADR
DRPRDRE
Trip value rec
Disturbance
B1-6RBDR
recorder
B6RBDR
Sequential of
events
Event recorder
Indications
Record no. N+100
Trip
Event
values
recordings
Section 15
Monitoring
Disturbance Report
FL
Fault locator
ANSI09000336-1-en.vsd
Disturbance
Fault locator
recording
en05000125_ansi.vsd
Event list
(SOE)
951