Function description
IEC 61850 generic communication I/O
functions
Introduction
The IEC 61850 generic communication I/O functions (DPGGIO) function block is
used to send double indications to other systems or equipment in the substation. It is
especially used in the interlocking and reservation station-wide logics.
Principle of operation
Upon receiving the input signals, the IEC 61850 generic communication I/O functions
(DPGGIO) function block will send the signals over IEC 61850-8-1 to the equipment
or system that requests these signals. To be able to get the signals, other tools must be
used, as described in the application manual, to PCM600 must be used to define which
function block in which equipment or system should receive this information.
Function block
DPGGIO
OPEN
POSITION
CLOSE
VALID
IEC07000200-2-en.vsd
IEC07000200 V2 EN
Figure 382:
DPGGIO function block
Input and output signals
Table 387:
DPGGIO Input signals
Name
Type
OPEN
BOOLEAN
CLOSE
BOOLEAN
VALID
BOOLEAN
Table 388:
DPGGIO Output signals
Name
Type
POSITION
INTEGER
IEC 61850
IEC 60617
identification
identification
DPGGIO
Default
Description
0
Open indication
0
Close indication
0
Valid indication
Description
Double point indication