Section 7
Current protection
7.3.4
7.3.5
Table 197:
EFPIOC (50N) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
Pickup
1 - 2500
Table 198:
EFPIOC (50N) Group settings (advanced)
Name
Values (Range)
MultPU
0.5 - 5.0
7.3.6
398
Input and output signals
Table 195:
EFPIOC (50N) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKAR
BOOLEAN
MULTPU
BOOLEAN
Table 196:
EFPIOC (50N) Output signals
Name
Type
TRIP
BOOLEAN
Setting parameters
Unit
Step
-
-
A
1
%IB
1
Unit
Step
-
0.1
Technical data
Table 199:
EFPIOC (50N) technical data
Function
Operate current
Reset ratio
Operate time
Reset time
Table continues on next page
Default
Description
-
Three phase currents
0
Block of function
0
Block from auto recloser
0
Enable current multiplier
Description
Trip signal
Default
Description
Disabled
Disable/Enable Operation
3000
Base current
200
Operate residual current level in % of IBase
Default
Description
1.0
Multiplier for operate current level
Range or value
(1-2500)% of lBase
> 95%
25 ms typically at 0 to 2 x I
set
25 ms typically at 2 to 0 x I
set
1MRK505222-UUS C
Accuracy
± 1.0% of I
at I £ I
n
n
± 1.0% of I at I > I
n
-
-
-
Technical reference manual