ABB Relion 670 Series Technical Reference Manual page 396

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 7
Current protection
7.2.5
Table 191:
OC4PTOC (51_67) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
1 - 99999
Vbase
0.05 - 2000.00
AngleRCA
40 - 65
AngleROA
40 - 89
NumPhSel
1 out of 3
2 out of 3
3 out of 3
DirModeSel1
Disabled
Non-directional
Forward
Reverse
Table continues on next page
390
Name
Type
PU_ST4
BOOLEAN
PU_A
BOOLEAN
PU_B
BOOLEAN
PU_C
BOOLEAN
PU_ST1_A
BOOLEAN
PU_ST1_B
BOOLEAN
PU_ST1_C
BOOLEAN
PU_ST2_A
BOOLEAN
PU_ST2_B
BOOLEAN
PU_ST2_C
BOOLEAN
PU_ST3_A
BOOLEAN
PU_ST3_B
BOOLEAN
PU_ST3_C
BOOLEAN
PU_ST4_A
BOOLEAN
PU_ST4_B
BOOLEAN
PU_ST4_C
BOOLEAN
2NDHARM
BOOLEAN
DIR_A
INTEGER
DIR_B
INTEGER
DIR_C
INTEGER
Setting parameters
Unit
Step
-
-
A
1
kV
0.05
Deg
1
Deg
1
-
-
-
-
Description
Common pickup signal from step4
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
Pickup signal from step1 phase A
Pickup signal from step1 phase B
Pickup signal from step1 phase C
Pickup signal from step2 phase A
Pickup signal from step2 phase B
Pickup signal from step2 phase C
Pickup signal from step3 phase A
Pickup signal from step3 phase B
Pickup signal from step3 phase C
Pickup signal from step4 phase A
Pickup signal from step4 phase B
Pickup signal from step4 phase C
Block from second harmonic detection
Direction for phase A
Direction for phase B
Direction for phase C
Default
Description
Disabled
Disable/Enable Operation
3000
Base current
400.00
Base voltage
55
Relay characteristic angle (RCA)
80
Relay operation angle (ROA)
1 out of 3
Number of phases required for phase
selection (1 of 3, 2 of 3, 3 of 3)
Non-directional
Directional mode of step 1 (Disabled, Nondir,
Forward, Reverse)
1MRK505222-UUS C
Technical reference manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670

Table of Contents