Section 9
Frequency protection
Name
Values (Range)
RestoreFreq
45.00 - 65.00
tRestore
0.000 - 60.000
tReset
0.000 - 60.000
9.3.6
566
Unit
Step
Hz
0.01
s
0.001
s
0.001
Technical data
Table 296:
SAPFRC (81) Technical data
Function
Operate value, pickup function
Operate value, internal blocking
level
Operate time, pickup function
Default
Description
49.90
Restore frequency if frequency is above
frequency value (Hz)
0.000
Restore time delay.
0.000
Time delay for reset.
Range or value
(-10.00-10.00) Hz/s
(0-100)% of VBase
100 ms typically
1MRK505222-UUS C
Accuracy
± 10.0 mHz/s
± 0.5% of V
n
-
Technical reference manual