ABB Relion 670 Series Technical Reference Manual page 391

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Technical reference manual
=
V
V
I
ref
_
A
A
dir A
_
ANSIEQUATION1452 V1 EN
=
V
V
I
ref B
_
B
dir B
_
ANSIEQUATION1453 V1 EN
=
V
V
I
ref C
_
C
dir C
_
ANSIEQUATION1454 V1 EN
The polarizing voltage is available as long as the positive-sequence voltage exceeds
4% of the set base voltage VBase. So the directional element can use it for all
unsymmetrical faults including close-in faults.
For close-in three-phase faults, the V1
sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is restored.
After 100 ms, the following occurs:
If the current is still above the set value of the minimum operating current
(between 10 and 30% of the set terminal rated current IBase), the condition seals in.
If the fault has caused tripping, the trip endures.
If the fault was detected in the reverse direction, the measuring element in
the reverse direction remains in operation.
If the current decreases below the minimum operating value, the memory resets
until the positive sequence voltage exceeds 10% of its rated value.
The directional setting is given as a characteristic angle AngleRCA for the function and
an angle window AngleROA.
=
I
A
=
I
B
=
I
C
memory voltage, based on the same positive
AM
Section 7
Current protection
(Equation 79)
(Equation 80)
(Equation 81)
385