ABB Relion 670 Series Technical Reference Manual page 451

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
7.6.3
7.6.4
Technical reference manual
Function block
SDEPSDE (67N)
I3P*
TRIP
V3P*
TRDIRIN
BLOCK
TRNDIN
BLKTR
TRVN
BLKTRDIR
PICKUP
BLKNDN
PUDIRIN
BLKVN
PUNDIN
PUVN
PUFW
PUREV
CND
VNREL
ANSI07000032-2-en.vsd
ANSI07000032 V2 EN
Figure 224:
SDEPSDE (67N) function block
Input and output signals
Table 208:
SDEPSDE (67N) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
BLKTRDIR
BOOLEAN
BLKNDN
BOOLEAN
BLKVN
BOOLEAN
Table 209:
SDEPSDE (67N) Output signals
Name
Type
TRIP
BOOLEAN
TRDIRIN
BOOLEAN
TRNDIN
BOOLEAN
TRVN
BOOLEAN
PICKUP
BOOLEAN
PUDIRIN
BOOLEAN
PUNDIN
BOOLEAN
PUVN
BOOLEAN
Table continues on next page
Default
Description
-
Group signal for current
-
Group signal for voltage
0
Blocks all the outputs of the function
0
Blocks the operate outputs of the function
0
Blocks the directional operate outputs of the function
0
Blocks the Non directional current residual outputs
0
Blocks the Non directional voltage residual outputs
Description
General trip of the function
Trip of the directional residual over current function
Trip of non directional residual over current
Trip of non directional residual over voltage
General pickup of the function
Pickup of the directional residual over current function
Pickup of non directional residual over current
Pickup of non directional residual over voltage
Section 7
Current protection
445

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670

Table of Contents