1MRK505222-UUS C
Technical reference manual
Reverse
Area
ANSI10000031 V1 EN
Figure 214:
Operating characteristic for fault directional element
Two relevant setting parameters for directional supervision element are:
•
Directional element is internally enable to operate as soon as I
40% of INDirPU and the directional condition is fulfilled in set direction.
•
Relay characteristic angle AngleRCA which defines the position of forward and
reverse areas in the operating characteristic.
Directional comparison step, built-in within directional supervision element, set
NS4PTOC (4612) output binary signals:
1.
PUFW=1 when tip of I2 phasor (operating quantity magnitude) is in forward area,
see fig
207
(Operating quantity magnitude is bigger than setting INDirPU)
2.
PUREV=1 when tip of I2 phasor (operating quantity magnitude) is in the reverse
area, see fig 207. (Operating quantity magnitude is bigger than 60% of setting
INDirPU)
AngleRCA
Forward
Area
Iop = I2
Section 7
Current protection
Vpol=-V2
ANSI10000031-1-en.vsd
is bigger than
Op
427