ABB Relion 670 Series Technical Reference Manual page 261

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Technical reference manual
The PHSEL input signal represents a connection of six different integer values from
Phase selection with load encroachment, quadrilateral characteristic function
FMPSPDIS (21) within the IED, which are converted within the zone measuring
function into corresponding boolean expressions for each condition separately. Input
signal PHSEL is connected to FMPSPDIS (21) function output signal PHSCND.
The input signal DIRCND is used to give condition for directionality for the distance
measuring zones. The signal contains binary coded information for both forward and
reverse direction. The zone measurement function filters out the relevant signals
depending on the setting of the parameter DirMode. Input signal DIRCND must be
configured to the STDIRCND output signal on ZDMRDIR (21D) function.
OffsetMhoDir=
Non-directional
DirMode=Offset
PHSEL
LoadEnchMode=
On/Off
LDCND
True
DIRCND
OffsetMhoDir=
Forward/Reverse
DirMode=
Forward/Reverse
BLKZ
BLOCK
ANSI11000216 V1 EN
Figure 126:
Simplified logic for release start signal
When load encroachment mode is switched on (LoadEnchMode=On) then start signal
PHSEL is also checked against LDCND signal.
Results of the directional measurement enter the logic circuits, when the zone operates
in directional (forward or reverse) mode, as shown in figure 126.
Composition of the phase pickup signals is presented in figure 81.
AND
AND
T
F
AND
OR
Impedance protection
AND
T
F
AND
Release
AND
ANSI11000216-1-en.vsd
Section 6
255