1MRK505222-UUS C
Table 48:
SMAI1 Non group settings (basic)
Name
Values (Range)
DFTRefExtOut
InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
DFTReference
InternalDFTRef
AdDFTRefCh1
AdDFTRefCh2
AdDFTRefCh3
AdDFTRefCh4
AdDFTRefCh5
AdDFTRefCh6
AdDFTRefCh7
AdDFTRefCh8
AdDFTRefCh9
AdDFTRefCh10
AdDFTRefCh11
AdDFTRefCh12
External DFT ref
ConnectionType
Ph-N
Ph-Ph
TYPE
1 - 2
Table 49:
SMAI1 Non group settings (advanced)
Name
Values (Range)
Negation
Disabled
NegateN
Negate3Ph
Negate3Ph+N
MinValFreqMeas
5 - 200
VBase
0.05 - 2000.00
Technical reference manual
Unit
Step
Default
-
-
InternalDFTRef
-
-
InternalDFTRef
-
-
Ph-N
Ch
1
1
Unit
Step
Default
-
-
Disabled
%
1
10
kV
0.05
400.00
Basic IED functions
Description
DFT reference for external output
DFT reference
Input connection type
1=Voltage, 2=Current
Description
Negation
Limit for frequency calculation in % of VBase
Base voltage