ABB Relion 670 Series Technical Reference Manual page 827

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
13.6.3
13.6.4
Technical reference manual
Function block
ECRWPSCH (85)
V3P*
IRVL
BLOCK
TRWEI
IFWD
ECHO
IREV
CR
WEIBLK1
WEIBLK2
LOVBZ
CBOPEN
CRL
ANSI06000289-1-en.vsd
ANSI06000289 V1 EN
Figure 408:
ECRWPSCH (85) function block
Input and output signals
Table 440:
ECRWPSCH (85) Input signals
Name
Type
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
IFWD
BOOLEAN
IREV
BOOLEAN
WEIBLK1
BOOLEAN
WEIBLK2
BOOLEAN
LOVBZ
BOOLEAN
CBOPEN
BOOLEAN
CRL
BOOLEAN
Table 441:
ECRWPSCH (85) Output signals
Name
Type
IRVL
BOOLEAN
TRWEI
BOOLEAN
ECHO
BOOLEAN
CR
BOOLEAN
Scheme communication
Default
Description
-
Group signal for voltage input
0
Block of function
0
A signal that indicates a forward fault has been
detected and will block tripping if there was a pre-
existing reverse fault condition (IREV)
0
A signal that indicates a reverse fault has been
detected and activates current reverasl logic
0
Block of WEI Logic
0
Block of WEI logic due to operation of other
protections that would effect a pilot trip or the detection
of reverse faults that will be tripped by an external device
0
Block of trip from WEI logic through the loss of voltage
(fuse-failure) function
0
Block of trip from WEI logic by an open breaker
0
POTT or Unblock carrier receive for WEI logic
Description
Operation of current reversal logic
Trip of WEI logic
A signal that indicates channel start (CS) by WEI logic
POR Carrier signal received from remote end
Section 13
821