ABB Relion 670 Series Technical Reference Manual page 655

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Technical reference manual
Name
Type
TR2P
BOOLEAN
TR3P
BOOLEAN
THOLHOLD
BOOLEAN
CBREADY
BOOLEAN
52a
BOOLEAN
PLCLOST
BOOLEAN
SYNC
BOOLEAN
WAIT
BOOLEAN
RSTCOUNT
BOOLEAN
MODEINT
INTEGER
Table 321:
SMBRREC (79) Output signals
Name
Type
BLOCKED
BOOLEAN
SETON
BOOLEAN
READY
BOOLEAN
ACTIVE
BOOLEAN
SUCCL
BOOLEAN
UNSUCCL
BOOLEAN
INPROGR
BOOLEAN
1PT1
BOOLEAN
2PT1
BOOLEAN
3PT1
BOOLEAN
3PT2
BOOLEAN
3PT3
BOOLEAN
3PT4
BOOLEAN
3PT5
BOOLEAN
PERMIT1P
BOOLEAN
PREP3P
BOOLEAN
CLOSECMD
BOOLEAN
WFMASTER
BOOLEAN
COUNT1P
INTEGER
COUNT2P
INTEGER
Table continues on next page
Default
Description
0
Signal to the AR that a two-pole tripping occurred
0
Signal to the AR that a three-pole tripping occurred
0
Holds the AR in wait state
0
CB must be ready for CO/OCO operation to allow
start / close
0
Status of the circuit breaker Closed/Open
0
Power line carrier or other form of permissive signal lost
0
Synchronism-check fulfilled (for 3Ph attempts)
0
Wait for master (in Multi-breaker arrangements)
0
Resets all counters
0
Integer input used to set the reclosingMode,
alternative to setting
Description
The AR is in blocked state
The AR operation is switched on, operative
Indicates that the AR function is ready for a new
sequence
Reclosing sequence in progress
Activated if CB closes during the time tUnsucCl
Reclosing unsuccessful, signal resets after the reclaim
time
Reclosing shot in progress, activated during open reset
Single-phase reclosing is in progress, shot 1
Two-phase reclosing is in progress, shot 1
Three-phase reclosing in progress, shot 1
Three-phase reclosing in progress, shot 2
Three-phase reclosing in progress, shot 3
Three-phase reclosing in progress, shot 4
Three-phase reclosing in progress, shot 5
Permit single-pole trip, inverse signal to PREP3P
Prepare three-pole trip, control of the next trip operation
Closing command for CB
Signal to Slave issued by Master for sequential
reclosing
Counting the number of single-phase reclosing shots
Counting the number of two-phase reclosing shots
Section 12
Control
649