ABB Relion 670 Series Technical Reference Manual page 783

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Name
Values (Range)
tUREvBufTout1
0.00 - 60.00
UREvCntThold2
1 - 100
tUREvBufTout2
0.00 - 60.00
UREvCntThold3
1 - 100
tUREvBufTout3
0.00 - 60.00
DelOldBufFull
No
Yes
ExtTimeFormat
LocalTime
UTC
DNPToSetTime
No
Yes
tSynchTimeout
30 - 3600
TSyncReqAfTout
No
Yes
Averag3TimeReq
No
Yes
PairedPoint
No
Yes
tSelectTimeout
1.0 - 60.0
tBrokenConTout
0 - 3600
tKeepAliveT
0 - 3600
Table 410:
MST2TCP Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
SlaveAddress
0 - 65519
MasterAddres
0 - 65519
ValMasterAddr
No
Yes
MasterIP-Addr
0 - 18
MasterIPNetMsk
0 - 18
Obj1DefVar
1:BISingleBit
2:BIWithStatus
Table continues on next page
Technical reference manual
Unit
Step
Default
s
0.01
5.00
-
1
5
s
0.01
5.00
-
1
5
s
0.01
5.00
-
-
No
-
-
UTC
-
-
No
s
1
1800
-
-
No
-
-
No
-
-
Yes
s
0.1
30.0
s
1
0
s
1
10
Unit
Step
Default
-
-
Disabled
-
1
1
-
1
1
-
-
Yes
IP
1
0.0.0.0
Address
IP
1
255.255.255.255
Address
-
-
1:BISingleBit
Section 12
Description
Unsolicited response class 1 event buffer
timeout
Unsolicited response class 2 event count
report treshold
Unsolicited response class 2 event buffer
timeout
Unsolicited response class 3 event count
report treshold
Unsolicited response class 3 event buffer
timeout
Delete oldest event when buffer is full
External time format
Allow DNP to set time in IED
Time synch timeout before error status is
generated
Time synchronization request after timeout
Use average of 3 time requests
Enable paired point
Select timeout
Broken connection timeout
Keep-Alive timer
Description
Disable/Enable Operation
Slave address
Master address
Validate source (master) address
Master IP-address
Master IP net mask
Object 1, default variation
Control
777

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670