Section 5
Differential protection
166
Phase-to-phase current variation
Phase-to-phase current variation one is main startup element. It covers most of the
abnormal status of the system. The phase-to-phase current variation fails in high
impedance faults, three-phase fault on weak side and switch onto fault on unloaded line
because of low sensitivity in these cases.
Phase-to-phase current variation takes the current samples as input and the signal is
evaluated using the sampling value based algorithm.
The phase-to-phase current variation criterion is shown below:
D
>
D + D
i
1.8
I
I
FF
T
ZD
EQUATION2255 V1 EN
Where:
Δi
sampling value of phase-to-phase current variation
ФФ
ΔI
setting of fixed threshold, which corresponds to setting
ZD
setting is 0.2·
ΔI
float threshold
T
It is the full-circle integral of the phase-to-phase current variation
-
1
2
T
1
å
D
=
D
I
|
i
(
t n
FF
T
T
=
n T
EQUATION2256 V1 EN
Where:
T
count of sample values in one cycle
Δi
is calculated using the below formula:
ФФ
D
=
-
-
i k
( ) [ ( )
i k
i k N
(
=
-
-
i k
( ) 2 (
i k N
EQUATION2257 V1 EN
N is the number of samples in one cycle.
IBase , where IBase is the base current.
-
) |
-
-
-
)] [ (
i k N
)
i k
(
+
-
)
i k
(
2 )
N
1MRK505222-UUS C
ICV> . The default value for the
-
2 )]
N
Technical reference manual