Minimum Operating Current - ABB Relion 670 Series Technical Reference Manual

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
6.2.2.3
Technical reference manual
X
Non-directional
IEC05000182 V1 EN
Figure 92:
Directional operating modes of the distance measuring zone

Minimum operating current

The operation of Distance measuring zone, quadrilateral characteristic for series
compensated lines (ZMCPDIS,ZMCAPDIS, 21) is blocked if the magnitude of input
currents fall below certain threshold values.
The phase-to-ground loop AG (BG or CG) is blocked if IA (IB or IC) < IMinPUPG.
For zone 1 with load compensation feature the additional criterion applies, that all phase-
to-ground loops will be blocked when IN < IMinOpIR, regardless of the phase currents.
IA (IB or IC) is the RMS value of the current in phase IA (IB or IC). IN is the RMS
value of the vector sum of the three phase currents, that is, residual current 3I0.
The phase-to-phase loop AB (BC or CA) is blocked if I
All three current limits IMinPUPG, IMinOpIR and IMinPUPP are
automatically reduced to 75% of regular set values if the zone is set to
operate in reverse direction, that is, OperationDir=Reverse.
X
R
Forward
Section 6
Impedance protection
X
R
Reverse
en05000182.vsd
< IMinPUPP.
AB (BC or CA)
R
201

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion red670

Table of Contents