ABB Relion 670 Series Technical Reference Manual page 420

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 7
Current protection
7.4.4
414
Input and output signals
Table 200:
EF4PTOC (51N67N) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
I3PPOL
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
BLK1
BOOLEAN
BLK2
BOOLEAN
BLK3
BOOLEAN
BLK4
BOOLEAN
MULTPU1
BOOLEAN
MULTPU2
BOOLEAN
MULTPU3
BOOLEAN
MULTPU4
BOOLEAN
52a
BOOLEAN
CLOSECMD
BOOLEAN
OPENCMD
BOOLEAN
Table 201:
EF4PTOC (51N67N) Output signals
Name
Type
TRIP
BOOLEAN
TRST1
BOOLEAN
TRST2
BOOLEAN
TRST3
BOOLEAN
TRST4
BOOLEAN
TRSOTF
BOOLEAN
PICKUP
BOOLEAN
PUST1
BOOLEAN
PUST2
BOOLEAN
PUST3
BOOLEAN
PUST4
BOOLEAN
PUSOTF
BOOLEAN
Table continues on next page
Default
Description
-
Three Phase Current Group Connection
-
Three Phase Voltage Group Connection
-
Three Phase Polarisation Current
0
General block
0
Block of trip
0
Block of step 1 (Pickup and trip)
0
Block of step 2 (Pickup and trip)
0
Block of step 3 (Pickup and trip)
0
Block of step 4 (Pickup and trip)
0
When activated, the pickup multiplier is in use for step1
0
When activated, the pickup multiplier is in use for step2
0
When activated, the pickup multiplier is in use for step3
0
When activated, the pickup multiplier is in use for step4
0
Breaker position
0
Breaker close command
0
Breaker open command
Description
Trip
Trip signal from step 1
Trip signal from step 2
Trip signal from step 3
Trip signal from step 4
Trip signal from switch onto fault function
General pickup signal
Pickup signal step 1
Pickup signal step 2
Pickup signal step 3
Pickup signal step 4
Pickup signal from switch onto fault function
1MRK505222-UUS C
Technical reference manual