ABB Relion 670 Series Technical Reference Manual page 592

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 10
Multipurpose protection
Name
Values (Range)
VoltageInput
Phase A
Phase B
Phase C
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
Phase AB
Phase BC
Phase CA
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
VBase
0.05 - 2000.00
OperHarmRestr
Disabled
Enabled
l_2nd/l_fund
10.0 - 50.0
EnRestrainCurr
Disabled
Enabled
RestrCurrInput
PosSeq
NegSeq
3*ZeroSeq
Max
RestrCurrCoeff
0.00 - 5.00
RCADir
-180 - 180
ROADir
1 - 90
LowVolt_VM
0.0 - 5.0
Operation_OC1
Disabled
Enabled
PickupCurr_OC1
2.0 - 5000.0
Table continues on next page
586
Unit
Step
Default
-
-
MaxPh
kV
0.05
400.00
-
-
Disabled
%
1.0
20.0
-
-
Disabled
-
-
PosSeq
-
0.01
0.00
Deg
1
-75
Deg
1
75
%VB
0.1
0.5
-
-
Disabled
%IB
1.0
120.0
1MRK505222-UUS C
Description
Select voltage signal which will be measured
inside function
Base Voltage
Disable/Enable operation of 2nd harmonic
restrain
Ratio of second to fundamental current
harmonic in %
Disable/Enable current restrain function
Select current signal which will be used for
current restrain
Restraining current coefficient
Relay Characteristic Angle
Relay Operate Angle
Below this level in % of Vbase setting
ActLowVolt takes over
Disable/Enable Operation of OC1
Pickup current for OC1 in % of Ibase