1MRK505222-UUS C
12.3.9.4
Technical reference manual
Input and output signals
Table 344:
QCRSV Input signals
Name
Type
EXCH_IN
INTEGER
RES_RQ1
BOOLEAN
RES_RQ2
BOOLEAN
RES_RQ3
BOOLEAN
RES_RQ4
BOOLEAN
RES_RQ5
BOOLEAN
RES_RQ6
BOOLEAN
RES_RQ7
BOOLEAN
RES_RQ8
BOOLEAN
BLK_RES
BOOLEAN
OVERRIDE
BOOLEAN
RES_DATA
INTEGER
Table 345:
QCRSV Output signals
Name
Type
RES_GRT1
BOOLEAN
RES_GRT2
BOOLEAN
RES_GRT3
BOOLEAN
RES_GRT4
BOOLEAN
RES_GRT5
BOOLEAN
RES_GRT6
BOOLEAN
RES_GRT7
BOOLEAN
RES_GRT8
BOOLEAN
RES_BAYS
BOOLEAN
ACK_TO_B
BOOLEAN
RESERVED
BOOLEAN
EXCH_OUT
INTEGER
Default
Description
0
Used for exchange signals between different BayRes
blocks
0
Signal for apparatus 1 that requests to do a reservation
0
Signal for apparatus 2 that requests to do a reservation
0
Signal for apparatus 3 that requests to do a reservation
0
Signal for apparatus 4 that requests to do a reservation
0
Signal for apparatus 5 that requests to do a reservation
0
Signal for apparatus 6 that requests to do a reservation
0
Signal for apparatus 7 that requests to do a reservation
0
Signal for apparatus 8 that requests to do a reservation
0
Reservation is not possible and the output signals are
reset
0
Signal to override the reservation
0
Reservation data coming from function block ResIn
Description
Reservation is made and the apparatus 1 is allowed to
operate
Reservation is made and the apparatus 2 is allowed to
operate
Reservation is made and the apparatus 3 is allowed to
operate
Reservation is made and the apparatus 4 is allowed to
operate
Reservation is made and the apparatus 5 is allowed to
operate
Reservation is made and the apparatus 6 is allowed to
operate
Reservation is made and the apparatus 7 is allowed to
operate
Reservation is made and the apparatus 8 is allowed to
operate
Request for reservation of other bays
Acknowledge to other bays that this bay is reserved
Indicates that the bay is reserved
Used for exchange signals between different BayRes
blocks
Section 12