Section 15
Monitoring
15.9.3
15.9.4
15.9.5
15.10
15.10.1
974
The indication function tracks 0 to 1 changes of binary signals during the recording
period of the collection window. This means that constant logic zero, constant logic
one or state changes from logic one to logic zero will not be visible in the list of
indications. Signals are not time tagged. In order to be recorded in the list of
indications the:
the signal must be connected to binary input(DRB1-6)
the DRP parameter Operation must be set Enabled
the DRP must be trigged (binary or analog)
Indications are selected with the indication mask (IndicationMask) when setting the
binary inputs.
The name of the binary signal that appears in the Indication function is the user-defined
name assigned at configuration of the IED. The same name is used in disturbance
recorder function (DR), indications (IND) and event recorder function (ER).
Function block
The Indications function has no function block of it's own. It is included in the
DRPRDRE block and uses information from the BxRBDR block.
Input signals
The Indications function logs the same binary input signals as the Disturbance report
function.
Technical data
Table 598:
technical data
Function
Buffer capacity
Event recorder
Introduction
Quick, complete and reliable information about disturbances in the primary and/or in
the secondary system is vital, for example, time-tagged events logged during
Maximum number of indications presented
for single disturbance
Maximum number of recorded disturbances
1MRK505222-UUS C
Value
96
100
Technical reference manual