ABB Relion 670 Series Technical Reference Manual page 862

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 13
Scheme communication
13.8.11.4
13.8.11.5
Table 489:
LCP3PTUC (37) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IBase
0 - 99999
PU_37
1.00 - 100.00
tUC
0.000 - 60.000
856
Input and output signals
Table 487:
LCP3PTUC (37) Input signals
Name
Type
I3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKTR
BOOLEAN
Table 488:
LCP3PTUC (37) Output signals
Name
Type
TRIP
BOOLEAN
TR_A
BOOLEAN
TR_B
BOOLEAN
TR_C
BOOLEAN
RI
BOOLEAN
BFI_A
BOOLEAN
PU_B
BOOLEAN
BFI_C
BOOLEAN
Setting parameters
Unit
Step
-
-
A
1
%IB
0.01
s
0.001
Default
Description
-
Three phase group signal for current inputs
0
Block all binary outputs by resetting timers
0
Block trip of the function
Description
Common trip signal
Trip signal from phase A
Trip signal from phase B
Trip signal from phase C
Common start signal
Pickup signal from phase A
Pickup signal from phase B
Pickup signal from phase C
Default
Description
Disabled
Operation Enable / Disable
3000
Current Base
50.00
Start value for 3 phase under current in %
IBase
0.000
Time delay to operate
1MRK505222-UUS C
Technical reference manual