ABB Relion 670 Series Technical Reference Manual page 991

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

1MRK505222-UUS C
Technical reference manual
SingleCmdFunc
OUTx
Pulse
SingleCmdFunc
OUTx
INPUT OUT
Pulse length >1s
I/O-
module
"Reset counter"
SMS settings
1.Operation = Off/On
2.tReporting = 0s...60min
3.Event Mask = No Events/Report Events
4.Scale = 1-90000
ANSI05000744 V1 EN
Figure 481:
Overview of the pulse counter function
The BLOCK and READ_VAL inputs can be connected to Single Command blocks,
which are intended to be controlled either from the station HMI or/and the local HMI.
As long as the BLOCK signal is set, the pulse counter is blocked. The signal connected
to READ_VAL performs one additional reading per positive flank. The signal must be
a pulse with a length >1 second.
The BI_PULSE input is connected to the used input of the function block for the
Binary Input Module (BIM).
The RS_CNT input is used for resetting the counter.
Each pulse counter function block has four binary output signals that can be connected
to an Event function block for event recording: INVALID, RESTART, BLOCKED
and NEW_VAL. The SCAL_VAL signal can be connected to the IEC Event function
block.
The INVALID signal is a steady signal and is set if the Binary Input Module, where
the pulse counter input is located, fails or has wrong configuration.
The RESTART signal is a steady signal and is set when the reported value does not
comprise a complete integration cycle. That is, in the first message after IED start-up,
in the first message after deblocking, and after the counter has wrapped around during
last integration cycle.
The BLOCKED signal is a steady signal and is set when the counter is blocked. There
are two reasons why the counter is blocked:
PulseCounter
BLOCK
INVALID
RESTART
READ_VAL
BLOCKED
NEW_VAL
BI_PULSE
RS_CNT
NAME
SCAL_VAL
Database
Pulse counter value:
0...2147483647
Section 16
Metering
EVENT
INPUT1
INPUT2
INPUT3
INPUT4
IEC EVENT
en05000744_ansi.vsd