ABB Relion 670 Series Technical Reference Manual page 450

Line differential protection ansi
Hide thumbs Also See for Relion 670 Series:
Table of Contents

Advertisement

Section 7
Current protection
INNonDirPU
UN_PU
OpMODE=INcosPhi
Pickup_N
INCosPhiPU
OpMODE=INVNCosPhi
INVNCosPhiPU
Phi in RCA +- ROA
OpMODE=IN and Phi
DirMode = Forw
Forw
DirMode = Rev
Rev
ANSI06000653 V1 EN
Figure 223:
Simplified logical diagram of the sensitive ground-fault current protection
444
When the function is activated binary output signal PUVN is activated. If the output
signals are active after the set delay tVNNonDir TRIP and TRUN are activated. A
simplified logical diagram of the total function is shown in figure 223.
AND
AND
AND
AND
OR
AND
0 - t
0
0 - t
0
OR
AND
TimeChar = InvTime
TimeChar = DefTime
1MRK505222-UUS C
t
SN
AND
AND
en06000653_ansi.vsd
Technical reference manual
PUNDIN
TRNDIN
PUVN
TRVN
PUDIRIN
TRDIRIN
PUFW
PUREV

Advertisement

Table of Contents
loading